HOME > Products > Power Transformer Testing
TWO-1100S Transformer Winding Ohmmeter
Maximum 100A current for measuring winding resistance of power transformer

Transformer Winding Ohmmeter is designed to measure the dc resistance of all types of magnetic windings accurately. It can test transformers and rotating machine windings and perform low-current resistance measurement on connections, contacts and control circuits. The maximum test current of TWO-1100S can be up to 100A.

+86 186 8208 3519 sales@haomaitest.com
  • Descriptions
  • Specifications
  • Download
  • Video
Descriptions

Transformer Winding Ohmmeter is designed to measure the dc resistance of all types of magnetic windings accurately. It can test transformers and rotating machine windings and perform low-current resistance measurement on connections, contacts and control circuits.

The main features of Transformer Winding Ohmmeter TWO-1100S are as follows:

●Adopt 4-wire method for resistance measurement

●DC test current up to 100 A maximum

●User-selectable maximum current range

●Resistance measurement from 30μΩ to 4Ω

●Able to save 1000 test results on-board 

●Fast auto safety discharge circuit

●Have overcurrent, overvoltage, discharge etc. protection functions

●Able to print the test results directly via built-in printer

Specifications

DC output range: 100A, 50A, 20A, 10A, 5A

Resistance measurement

30μΩ-100mΩ @ 100A

100μΩ-200mΩ @ 50A

200μΩ-1Ω @ 20A

500μΩ-2Ω @ 10A

2mΩ-4Ω @ 5A

Measuring accuracy: ±0.2% reading ± 2μΩ

Resolution: 0.1μΩ

320×240 colour LCD screen for display

USB port for downloading results

Built-in printer for printing test results directly 

Max. memory capacity: 1000 test results

Power supply: customized(AC220V/230V±10%, 50Hz/60Hz optional) 

Dimension: 400x225x350mm(15.75x8.86x13.78 in)

Weight: 19.5kg(42.99 lb)

Environmental Conditions

storage temperature: -20~60

humidity: <90%

operating temperature: -10~50

Safety Qualifications and EMC

Safety: designed in accordance with IEC61010-1

EMC: light industrial IEC 61326

 

Transformer Winding Ohmmeter TWO-1100S is used for measuring winding resistance of power transformer, which the maximum test current can be up to 100A.

Copyright © 2020 HAOMAI ELECTRIC TEST EQUIPMENT CO.,LTD All rights Reserved.