HOME > Products > IEC 61850 Testing
RELAYSTAR-6000D IEC 61850 Test System
Test solution for IEC 61850-based protection devices and Merging Unit

The RELAYSTAR-6000D is new generation test set dedicated to IEC 61850-based protection devices and Merging Unit. It can simulate various types of messages which conforms to IEC 61850-9-1/9-2/9-2LE, GOOSE, IEC 60044-7/8 FT3.

+86 186 8208 3519 sales@haomaitest.com
  • Descriptions
  • Specifications
  • Download
  • Video
Descriptions

The RELAYSTAR-6000D is new generation test set dedicated to IEC 61850-based protection devices and Merging Unit. It can simulate various types of messages which conforms to IEC 61850-9-1/9-2/9-2LE, GOOSE, IEC 60044-7/8 FT3.

IEC 61850 Test System RELAYSTAR-6000D can either be operated by embedded industrial PC with 9.7’’ touch screen or by test software running on a PC.

The time synchronization modes GPS, IRIG-B code and IEEE1588 are supplied along with RELAYSTAR-6000D, which makes both substation internal debugging and substation to substation joint debugging available.

The main features of IEC 61850 Test System RELAYSTAR-6000D are as follows:

●IEC 61850-based protection devices & MU can be tested

●Embedded industrial PC with 9.7’’ touch screen

●Both local test and PC remote test available

●Able to simulate various types of messages which conforms to IEC 61850-9-1/9-2/9-2LE, GOOSE, IEC 60044-7/8 FT3

●12 low level analog outputs

●Four time synchronization modes: in-built GPS, IRIG-B code, PPS and IEEE1588

●Small size and light weight(only 4kg / 8.82lb) 

Specifications

Ethernet Communication Interfaces

Mode

10/100Base-TX(10/100Mbit,twisted-pair,auto-crossover)

Number of port

2

Type of interface

RJ45

Status indication

LED lights

 

Optical Fiber Communication Interfaces

Mode   

100Base-FX (100Mbit, optical fiber, full duplex)

Number of port

16

Type of interface

ST

Fiber type

62.5/125μm(multi-mode fiber)

Wavelength

1310nm

Transmission distance

>1km

Status indication

LED lights

 

FT3 Interfaces

Number of port 

10 (8 for transmitting, 2 for receiving)

Type of interface

ST

Fiber type

62.5/125μm (multi-mode fiber)

Wavelength

850nm

 

Low Level Analog Outputs

Number of outputs

12

Setting range

AC: 0~7.07Vrms; DC: 0~10V

Current at max. burden

1mA

Accuracy

<0.05%

Resolution

250μV

Distortion (THD+N)

<0.1%

Frequency

Sinusoidal signal: 10~1000Hz

Transient signal: DC~10.0kHz

Accuracy: <0.002%(under power frequency, error 1mHz)

Resolution: 0.001Hz

Phase

Range of phase angle: 0 ~359. 9°

Accuracy: <0.1°, 50/60Hz

Resolution: ±0.01°

 

Binary Inputs

Number

10

Type

potential-free contact or idle contact (automatic identification)

Threshold characteristics

“0”: 06V; “1”:12V250V

 

Binary Outputs

Number

4

Type

idle contact(fast contact output optional)

Break capacity

250VAC/0.5A; 250VDC/0.2A

 

Power Supply

Nominal input voltage

customized (AC230V/120V±10%, 1-phase)

Nominal frequency

50/60 Hz

Rated current

10A at 230V / 12A at 120V

Connection

Standard AC socket (IEC 60320)

 

Environmental Conditions

Operation temperature

0 ... +50 °C (+32 ... +122 °F)

Storage temperature

-25 ... +70 °C (-13 ... +158 °F)

Humidity range

relative humidity 5 ... 95 %, non-condensing

Vibration

IEC 60068-2-6(20m/s2 at 10 ... 150 Hz)

 

Miscellaneous

Weight

4kg(8.82 lb)

Dimensions (W x H x D, without handle)

345×135×270mm(13.58x5.31x10.63 in)

 

IEC 61850 Protection Relay Test System RELAYSTAR-6000D focuses on the real-time communication methods of GOOSE and Sampled Values to interface with the devices under test.

Copyright © 2020 HAOMAI ELECTRIC TEST EQUIPMENT CO.,LTD All rights Reserved.